Energy Storage Power Conversion Boost System

Technical Features
● Be capable of adjusting peak and frequency, black start
● Be customized to meet the different needs of customers
● Integrated with the step-up transformer, PCS and incoming line
● With perfect communication, monitoring, management, control, early warning and protection functions; be capable of long-term sustainable and safe operation, and detecting the system operation status through the upper computer; be provided with perfect data analysis capabilities and emergency power supply function
Container Power |
2500kW |
3450kW |
DC Parameters |
||
Battery Voltage Range |
500Vdc-850Vdc |
1164.8Vdc-1497.6Vdc |
Maximum Charge/Discharge Current |
4800A |
3872A |
Ac Parameters (Grid-connected) |
||
Rated Output Power |
2500kW |
3450kW |
Maximum Apparent Power |
2750kVA |
3795kVA |
Rated Voltage |
10kVac |
|
Voltage Range |
10.7±0.4kVA( 35kV optional) |
|
Rated Current |
144.3A |
199.2A |
Maximum Output Current |
158.7A |
219.1A |
Rated Output Frequency |
50/60Hz |
|
Frequency Range |
45-55/55-65Hz |
|
Basic Parameters |
||
Size(L*W*H) |
2600/6058/2896mm |
2600/6067/2896mm |
Weight |
16T |
20T |
Boost Transformer Capacity |
2750kVA |
3750kVA |